2000 IEEE ESMO - 2000 IEEE 9th International Conference on Transmission and Distribution Construction, Operation and Live-Line
DOI: 10.1109/tdcllm.2000.882835
|View full text |Cite
|
Sign up to set email alerts
|

On-line testing of on-load tap changers with a portable acoustic system

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
4
1

Citation Types

0
6
0
4

Publication Types

Select...
4
3

Relationship

0
7

Authors

Journals

citations
Cited by 14 publications
(10 citation statements)
references
References 0 publications
0
6
0
4
Order By: Relevance
“…The most common operational problems connected with OLTC may be presented as follows: wear or damage of the main contacts, wear of the resistance contacts, break or improper pull of the power springs, defects of the power transmission system (clearance on transmissions, the Cardan joints etc.) [1][2][3][4][5][6].…”
Section: Introductionmentioning
confidence: 99%
See 1 more Smart Citation
“…The most common operational problems connected with OLTC may be presented as follows: wear or damage of the main contacts, wear of the resistance contacts, break or improper pull of the power springs, defects of the power transmission system (clearance on transmissions, the Cardan joints etc.) [1][2][3][4][5][6].…”
Section: Introductionmentioning
confidence: 99%
“…Therefore, it becomes necessary to look for new diagnostic methods for the on-line assessment of the OLTC operation condition, e.g. without shutting-down the transformer under study [1,3,7]. * corresponding author; e-mail: a.cichon@po.opole.pl A method which makes online diagnosis of devices possible is the acoustic method; it is applied for technical condition evaluation of power transformer windings insulation with regard to partial discharges appearance.…”
Section: Introductionmentioning
confidence: 99%
“…When compared with other OLTC vibration monitoring methods, the proposed technique needs only the initial interval of the signal (interval a), reducing the computational time, and simplifying the classifier system, that will not process the sinal envelope, as proposed on [6], [1], [4] and [5], but only the 9 parameters obtained for the a interval.…”
Section: E Analysis Of the Experimental Resultsmentioning
confidence: 99%
“…On this approach, the vibration signals emitted during the tap changes are recorded and post-processed using spectral analysis and some pattern classifier technique. Some existing works use Wavelet transform [4], [5], [1], or Hilbert convolution [6] for the signal envelope detection, and a neural network to classify the OLTC condition. This paper describes a new method of analysis for the vibration signals, using a Genetic Algorithm as a function estimator.…”
Section: Introductionmentioning
confidence: 99%
“…The dissolved gas-in-oil analysis (DGA) is the most popular technique for on-line OLTC diagnosis [4]. However, in recent years, many researchers [1], [5], [6], have been investigating non-invasive monitoring and analysis of these devices based on vibration signal analysis techniques, which can avoid unnecessary and inconvenient opening of tap changers. The holler contacts can take up only one fixed contact or two adjacent fixed contacts.…”
Section: Introductionmentioning