Islanding detection technique based on superimposed components of voltage

Abstract: This study presents a new islanding detection technique based on islanding discrimination factor which is derived from the superimposed components of voltages. These voltages are calculated by utilising the acquired voltage signals from the terminal of distributed generators. Various islanding and non-islanding events with varying power mismatches have been simulated on two different widely used networks namely (i) IEEE 34 bus network and (ii) IEC61850-7-420 Micro-Grid model in real time digital simulator (RTD… Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
2
1
1
1

Citation Types

0
28
0

Year Published

2019
2019
2022
2022

Publication Types

Select...
6
1

Relationship

0
7

Authors

Journals

citations
Cited by 30 publications
(29 citation statements)
references
References 31 publications
0
28
0
Order By: Relevance
“…The realised IDF module converts voltage magnitude to the superimposed components of voltages (ΔV A , ΔV B and ΔV C ) given by (1)-(3). These superimposed components are computed using sliding window techniques, in which data of the current window is updated by the data of the previous window [22]…”
Section: Digital Design Of the Proposed Idt Algorithmmentioning
confidence: 99%
See 2 more Smart Citations
“…The realised IDF module converts voltage magnitude to the superimposed components of voltages (ΔV A , ΔV B and ΔV C ) given by (1)-(3). These superimposed components are computed using sliding window techniques, in which data of the current window is updated by the data of the previous window [22]…”
Section: Digital Design Of the Proposed Idt Algorithmmentioning
confidence: 99%
“…The obtained results are summarised in Table 2. Maximum detection time of islanding is ∼14 ms, which is less than the suggested technique (∼22.5 ms) of [17,22]. Similarly, the performance of the proposed IDT has also been tested for critical non-islanding events, i.e.…”
Section: Performance Verification Of Prototype Under Active Power Imbmentioning
confidence: 99%
See 1 more Smart Citation
“…The proposed harmonic filter-based impedance method has been compared with other islanding detection techniques such as OUV/ OUF, traditional impedance measurement technique, superimposed components methods [16], Kalman filter-based islanding detection technique [19] for various islanding and non-islanding scenarios including system transients in the six bus test microgrid system shown in Fig. 4.…”
Section: Comparison With Existing Islanding Detection Techniquesmentioning
confidence: 99%
“…In recent years studies relating to PQ disturbances detection and event recognition are documented in several references …”
Section: Introductionmentioning
confidence: 99%