2024
DOI: 10.1177/07349041241238151
|View full text |Cite
|
Sign up to set email alerts
|

Analysis of fire extinguishing performance and mechanisms in transformer oil pool fires by large-scale compressed nitrogen foam: Impact of different nozzle pressures

Fengju Shang,
Jiaqing Zhang,
Taiyun Zhu
et al.

Abstract: This article investigates the suppression of transformer oil pool fires using compressed nitrogen aqueous film-forming foam extinguishing agents with varying nozzle pressures (0.1–0.4 MPa), and a comprehensive analysis of fire extinguishing behavior and resistance to re-ignition was conducted. The research findings indicate that at a nozzle pressure of 0.4 MPa, there is a significant enhancement in fire extinguishing efficiency, with a reduction in extinguishing time by 15.0%–29.2%, and an increase in resistan… Show more