2016
DOI: 10.5370/kiee.2016.65.10.1780
|View full text |Cite
|
Sign up to set email alerts
|

Analysis of Diagnosis and Very Low Frequency Experiment to Detect of Fault on 22.9kV Class Cable

Abstract: -This paper presents few case studies of state diagnosis of XLPE cables using very low frequency techniques. The power cables of 22.9kV which have installation fault were assessed using VLF technique in addition to other techniques like insulation resistance and DC voltage withstand test. From the experimental results, The dielectric loss(tanδ) values of degradation of the cable(joint, knife, needle) at U 0 were 5.839, 5.526 and 6.251, respectively and all values were "further study advised". VLF PD measuremen… Show more