Abstract: On the JD267 distribution transformer with a capacity of 100 kVA at the Kalibaru feeder on the PT PLN (Persero) ULP Genteng experienced  overloading at WBP (88.03%) and high voltage losses. The magnitude of the load exceeds 80% of the standard transformer capacity and is in the bad category (load >= 80%) according to Table I. SE No. 0017.E/DIR/2014, related to transformer loading percentage. Meanwhile, the voltage loss of the JD267 transformer when the WBP is in Phase R is 19.05%, Phase S is 17.08%, and Pha… Show more