As buildings are growing higher and larger, more composite structures have been used. However, the steel member used for composite structure tends to rapidly lose its strength at elevated temperatures. For this reason, it is required to apply a fire resistance mechanism, but it is difficult to implement because of the cost and technical limitations in the case of fire-resistant paint. In case of fireproof spray coat, scattering phenomena, poor work conditions for wet application, and construction delay are the main challenges to be addressed. In this study, a full-scale fire resistance test of non-fire resistant cladding column was conducted in accordance with KS F 2257-7. According to the test results, the specimens CC-01, CC-02, and CC-03 failed to meet the requirements for a 3-hour fire resistance rating because of the joint deformation and less cover thickness, while CC-04, CC-05, and CC-06 with increased thickness and reinforced joints satisfied the requirements for a 3-hour fire resistance rating.