2013
DOI: 10.14346/jkosos.2013.28.6.011
|View full text |Cite
|
Sign up to set email alerts
|

A Study on the Reliability Analysis for Smoke Detector using Dust

Abstract: : This paper presents a study on the analyzing reliability of smoke fire detector using accelerated life test. In general, the smoke fire detector is broken by dust which flow in smoke detection chamber. In order to conduct accelerated life test of smoke fire detector dust is set accelerated factor in this paper. The dust is fly-ash which is test particle 5th regulated by KS A 0090. The dust accelerated level is 60 g, 180 g and 360 g and failure time is measured by smoke sensitivity testing. It is considered t… Show more