A study of off-design performance improvement for a centrifugal refrigerant compressor

Abstract: This study numerically investigates the effects of changing vaned diffuser angles and vaneless diffuser widths of a twostage centrifugal refrigerant compressor on the reduction of surge flow rate and the improvement of part-load performance. The first stage has a low-solidity vaned diffuser, while the second stage has a vaneless diffuser. The analysis results show that adjusting the angle of low-solidity vaned diffuser in the first stage can lower the surge flow rate and keeps high efficiencies at low flow rat… Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
4
1

Citation Types

0
5
0

Year Published

2018
2018
2024
2024

Publication Types

Select...
6
1

Relationship

1
6

Authors

Journals

citations
Cited by 7 publications
(5 citation statements)
references
References 17 publications
(14 reference statements)
0
5
0
Order By: Relevance
“…It has been observed that, at low mass flow rates, the de-swirler vane influences the upstream flow structure of the vaneless diffuser and return channel [46]. Hung [47] suggested that, in the case of a vaned diffuser, the vane angle must be increased to reduce the surge mass flow rate. The IGV can have a beneficial effect if not combined with the previous parameter, but the width reduction of the second vaned diffuser can also be beneficial.…”
Section: Two Stagementioning
confidence: 99%
“…It has been observed that, at low mass flow rates, the de-swirler vane influences the upstream flow structure of the vaneless diffuser and return channel [46]. Hung [47] suggested that, in the case of a vaned diffuser, the vane angle must be increased to reduce the surge mass flow rate. The IGV can have a beneficial effect if not combined with the previous parameter, but the width reduction of the second vaned diffuser can also be beneficial.…”
Section: Two Stagementioning
confidence: 99%
“…Yet, in subtropical or tropical zones, centrifugal chillers may work all year round. However, the full-load running period of the chiller is usually shorter than one month during a whole year operation, meaning that most of the time, chillers are in part-load operation [1]. Hence, for more effective characterization of a chiller in association with the part-load operation, implementation of integrated part-load value (IPLV) [2] is adopted as the design concept.…”
Section: Introductionmentioning
confidence: 99%
“…Hence, for more effective characterization of a chiller in association with the part-load operation, implementation of integrated part-load value (IPLV) [2] is adopted as the design concept. The IPLV is defined as follows IPLV = 0.01A + 0.42B + 0.45C + 0.12D (1) where A is the coefficient of performance (COP) at 100% load, B is the COP at 75% load, C is the COP at 50% load, and D is the COP at 25% load. From Equation (1), the proportions of 75% and 50% part-loads are much higher than full-load or 25% load.…”
Section: Introductionmentioning
confidence: 99%
See 1 more Smart Citation
“…Compressor off-design conditions have been thoroughly studied experimentally and numerically. [5][6][7][8] However, less research has been devoted to the analysis of extreme off-design points outside the standard corrected maps. Experimentally, it is hard to measure extreme off-design conditions due to different reasons depending on the region of the map, although some authors have been able to characterize extended maps.…”
Section: Introductionmentioning
confidence: 99%