volume 11, issue 3, P1224-1231 1996
DOI: 10.1109/61.517475
View full text
|
|
Share

Abstract: Faults applied during March 1993 commissioning tests for the California-Oregon Transmission Project produced 14 Hz transient oscillations that were conspicuous in BPA's enhanced transducers at Malin, and in PG&E's Dynamic System Monitor at Table Mountain. Prony analysis of high speed fault data provided a detailed model for the underlying network resonance signal, and a basis for validating transient performance of a Macrodyne Phasor Measurement Unit (PMU) at the test site. This instrument, which is closely as…

Expand abstract