volume 10, issue 2, P1031-1037 1995
DOI: 10.1109/61.400825
View full text
|
|
Share

Abstract: A study of the potential for control interaction between a proposed TCSC and an existing SVC is presented. The results indicate that a control interaction exists between the voltage-input PSDC of the TCSC, the series compensated ac system resonances, and the SVC controls. The addition of recommended filtering and synthesized angle-input PSDC showed improved pe $0 rmance.