Volume 1: Heat Transfer in Energy Systems; Thermophysical Properties; Theory and Fundamental Research in Heat Transfer 2013
DOI: 10.1115/ht2013-17061
View full text |Buy / Rent full text
|
Sign up to set email alerts
|

Abstract: Energy Conservation Measures (ECMs) of the primary data center at the University of Maryland are developed. Measurement and simulation are performed to validate the developed ECMs. Three ECMs — 1) Increase in the return temperature at Computer Room Air Conditionings (CRACs) 2) Cold aisle containment 3) Elimination of unnecessary CRACs — are suggested to reduce energy consumption by optimizing the thermo-fluid flow in the data center. Power savings of 12.7 kW – 17.4 kW and 14.1 kW are obtained by increasing the… Show more