An Improved Distributed Secondary Control Method for DC Microgrids With Enhanced Dynamic Current Sharing Performance

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
2
2
1

Citation Types

0
164
0
1

Year Published

2016
2016
2022
2022

Publication Types

Select...
4
4

Relationship

0
8

Authors

Journals

citations
Cited by 312 publications
(168 citation statements)
references
References 34 publications
0
164
0
1
Order By: Relevance
“…Equation (29) shows that deviation of output voltage results from the current difference going through a low pass filter G d (S) and dc gain K DC . The longer decay time constant t is, the more accurate current sharing can be achieved, but on the other hand, the larger voltage deviation happens.…”
Section: Analysis Of the Proposed Current Sharing Control Systemmentioning
confidence: 99%
See 1 more Smart Citation
“…Equation (29) shows that deviation of output voltage results from the current difference going through a low pass filter G d (S) and dc gain K DC . The longer decay time constant t is, the more accurate current sharing can be achieved, but on the other hand, the larger voltage deviation happens.…”
Section: Analysis Of the Proposed Current Sharing Control Systemmentioning
confidence: 99%
“…The longer decay time constant t is, the more accurate current sharing can be achieved, but on the other hand, the larger voltage deviation happens. To guarantee that the voltage deviation does not exceed its maximum acceptable value, the value of the decay time constant should be limited according to (19), (20) and (29).…”
Section: Analysis Of the Proposed Current Sharing Control Systemmentioning
confidence: 99%
“…The effect of the communication delay Td on previous communication channel based secondary control methods are discussed in [16]- [18]. In this subsection, the impact of the communication delay on the stability is analyzed using eigenvalue analysis.…”
Section: Effect Of Communication Delaymentioning
confidence: 99%
“…Thus, even a small difference in the output voltage between the paralleled sources will cause the one that is a few mV higher to hog all the current. The lower the output voltage of the module is, the more severe this problem is [10].…”
Section: Introductionmentioning
confidence: 99%
“…To address the aforementioned challenges, different control schemes for DC microgrids are reported in [7,[10][11][12][13][14][15][16]. Commonly, these control schemes can be categorized as centralized and decentralized control [10][11][12][13][14][15][16][17][18][19][20][21].…”
Section: Introductionmentioning