Abstract-There is a need for a new survey of conditionmonitoring methods for circuit breakers and disconnectors, since during the last two decades less than ten surveys have been carried out. The paper presents several statistical surveys and analyses. The methods of condition monitoring found are reviewed and classified according to the different types of failure identified in the surveys. Some research gaps are identified, such as the prediction of the degradation of the contacts, the signal processing of coil and motor currents and the switching.
This paper presents a method that can be used to rank disconnectors in the electric power system, according to the condition of one of the most critical parts, the contacts. The temperature of the contacts can be continuously measured by a new type of infrared sensor. For the case study, 54 sensors were placed on six disconnectors together with reference sensors measuring the ambient temperature. The measured temperature at each contact is then regressed against the ambient temperature and the current through the disconnector. Both a linear and a quadratic dependency of the current are tested and the quadratic one explains the data best. The coefficient of the current serves as a measure of the condition of the contact. Then, it becomes possible to identify in which contacts the resistance has increased the most. As a consequence, it is possible to make better maintenance decisions for the disconnectors.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.